Fire Code, O Reg 213/07
Door in a fire separation
2.2.3.4. (1) A door in a fire separation shall be kept closed when not in use.
- (2) A door in a fire separation shall be checked as frequently as necessary to ensure that the door remains closed.
- (3) Sentences (1) and (2) do not apply to
- (a) a door designed to close automatically in the event of a fire emergency, or
- (b) a door for which an approved fire safety plan contains provisions for closing in the event of a fire emergency.
- (4) A door in a fire separation shall be inspected monthly.
- (5) A door opening in a fire separation and the areas surrounding the door opening shall be kept clear of anything that would be likely to obstruct or interfere with the free operation of the door.
City of Kitchener Fire Department v Terrace Good, 2015 CanLII 106163 (ON FSC)
7. The Inspection Order served by the Appellant identified the following reasons, as specified in Appendix A of the Order:
- 3. Door closures comply with Fire Code O. Reg. 213/07, Div. B 2.2.3.2 (c).
- Closures in fire separations shall be maintained to ensure they are operable at all times by making necessary adjustments and repairs to door hardware and accessories to ensure proper closing and latching.
- 3. Door closures comply with Fire Code O. Reg. 213/07, Div. B 2.2.3.2 (c).
- Comment: All fire rated doors shall be tested, adjusted and maintained to ensure they close and latch upon release. All gapping shall be reduced to 6mm clearance beneath and not more than 3 mm at the top and sides.
18. The Commission grants the application and authorizes the Appellant to complete, on or after January 20, 2016, all work set out in the Inspection Order dated February 12, 2014, if the Respondent does not remedy all deficiencies on or before January 19, 2016.